Customization: | Available |
---|---|
Output Type: | Single |
Warranty: | 3 Years |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
NDR-240 240W Rail Type Switching Power Supply | ||||
Project | Technical Index | |||
Output | DC voltage | 12V | 24V | 48V |
Rated current | 20A | 10A | 5A | |
Rated power | 240W | 240W | 240W | |
Ripple and noise | <120mV | <120mV | <150mV | |
Voltage accuracy | ±2% | ±1% | ||
Output voltage regulation range | ±10% | |||
Load adjustment rate | ±1% | |||
Linear adjustment rate | ±0.5% | |||
Input | Voltage range | 85-264VAC 47hz-63hz (120vdc-370vdc: DC input can be realized by connecting AC / L +, AC / N (-)) | ||
Efficiency (typical) | >86% | >88% | >89% | |
Working current | <2.25A 110VAC <1.3A 220VAC | |||
Impulse current | 110VAC 20A, 220VAC 35A | |||
Start, rise, hold time | 500ms,70ms,32ms :110VAC/500ms,70ms,36ms :220VAC | |||
Protect | overload protection | 105% - 150% type: protection mode: automatic recovery after removing the abnormal condition of constant current mode | ||
Overvoltage protection | When the output voltage is more than 135%, the output will be turned off. It will recover automatically after the abnormal conditions are removed | |||
Short circuit protection | +VOWhen the abnormal condition of output is released, it will recover automatically | |||
Environmental | Working temperature and humidity | -10ºC~+60ºC;20%~90RH | ||
Storage temperature and humidity | -20ºC~+85ºC;10%~95RH | |||
Safety/EMC | Withstand voltage | Input output: 3kVac input ground: 1.5kVac output ground: 0.5kvac for 1 minute | ||
Leakage current | <1mA/240VAC | |||
Isolation resistance | Input output, input shell, output shell: 500VDC / 100M Ω | |||
Other | size | 60*125*114mm | ||
Net weight / gross weight | 0.95/1000g |