| DR-480 480W Din Rail Power Supply | |||
| Project | Technical index | ||
| Output | DC voltage | 24V | 48V |
| Rated current | 20A | 10A | |
| Rated power | 480W | 480W | |
| Ripple and noise | <120mV | <240mV | |
| Voltage accuracy | ±1% | ±1% | |
| Ripple and noise | ±10% | ||
| Load adjustment rate | ±1% | ||
| Linear adjustment rate | ±0.5% | ||
| Input | Voltage range / frequency | 180-264VAC 47Hz~63Hz (270VDC~370VDC) | |
| Efficiency (typical) | >84% | >86% | |
| Working current | <2.5A 110VAC <1.3A 220VAC | ||
| Impulse current | 110VAC 20A, 220VAC 35A | ||
| Leakage current | 3000ms,100ms,22ms :110VAC/1500ms,100ms,28ms :220VAC | ||
| Protect | overload protection | 105%-150% Type:production mode:burp modde automatic recovery after the abnormal condition is lifted | |
| Overvoltage protection | Output Voltage>135% will be restored automatically after it is removed | ||
| Short circuit protection | VO The output abnormal condition will be restored automatically after it is removed after the power is restarted | ||
| Over temperature protection | Turn off the output temperature when it is over 85°and recover after eht power is restarted | ||
| Environmental Science | Working temperature and humidity | -10ºC~+50ºC;20%~90RH | |
| Storage temperature and humidity | -20ºC~+85ºC;10%~95RH | ||
| Safety regulations | Withstand voltage | I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P:0.5KVAC | |
| leakage current | <1.5mA/240VAC | ||
| Insulation impedance | I/P-O/P, O/P-Shell, O/P-Shell :500VDC/100MΩ | ||
| Other | size | 125.5*100*125.2mm | |
| Net weight / gross weight | 1200/1230g | ||