Customization: | Available |
---|---|
Output Type: | Single |
Warranty: | 3years |
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
15W Ultra Slim Step Shape DlN Rail HDR - 15 series |
||||||||
SPEClFlCATlON | ||||||||
MODEL | HDR-15-5 | HDR-15-12 | HDR-15-15 | HDR-15-24 | HDR-15-48 | |||
OUTPUT | DC VOLTAGE | 5V | 12V | 15V | 24V | 48V | ||
RATED CURRENT | 2.4A | 1.25A | 1A | 0.63A | 0.32A | |||
CURRENT RANGE | 0 ~ 2.4A | 0 ~ 1.25A | 0 ~ 1A | 0 ~ 0.63A | 0 ~ 0.32A | |||
RATED POWER | 12W | 15W | 15W | 15.2W | 15.4W | |||
RlPPLE & NOlSE(max.) Note.2 | 80mVp-p | 120mVp-p | 120mVp-p | 150mVp-p | 240mVp-p | |||
VOLTAGE ADJ. RANGE | 4.5 ~ 5.5V | 10.8 ~ 13.8V | 13.5 ~ 18V | 21.6 ~ 29V | 43.2 ~ 55.2V | |||
VOLTAGE TOLERANCE Note.3 | ±2.0% | ±1.0% | ±1.0% | ±1.0% | ±1.0% | |||
LlNE REGULATlON | ±1.0% | ±1.0% | ±1.0% | ±1.0% | ±1.0% | |||
LOAD REGULATlON | ±1.0% | ±1.0% | ±1.0% | ±1.0% | ±1.0% | |||
SETUP, RlSETlME | 2000ms, 80ms/230VAC 2000ms, 80ms/115VAC at full load | |||||||
HOLD UP TlME(TYP.) | 30ms/230VAC 12ms/115VAC at full load | |||||||
lNPUT | VOLTAGE RANGE | 85 ~ 264VAC(277VAC operational ) 120 ~ 370VDC(390VDC operational ) | ||||||
FREQUENCY RANGE | 47 ~ 63Hz | |||||||
EFFlClENCY(TYP.) | 80% | 85% | 85.5% | 86% | 87% | |||
AC CURRENT(TYP.) | 0.5A/115VAC 0.25A/230VAC | |||||||
lNRUSH CURRENT(TYP.) | COLD START 25A/115VAC 45A/230VAC | |||||||
PROTECTlON | OVERLOAD | 110 ~ 145% rated output power | ||||||
Hiccup mode when output voltage <50%, recovers automatically after fault condition is removed Constant current limiting within 50% ~100% rated output voltage, recovers automatically after fault condition is removed |
||||||||
OVER VOLTAGE | 5.75 ~ 6.75V | 14.2 ~ 16.2V | 18.8 ~ 22.5V | 30 ~ 36V | 56.5 ~ 64.8V | |||
Protection type : Shut offo/p voltage, clamping by zener diode | ||||||||
ENVlRONMENT | WORklNG TEMP. | -30 ~ +70ºC(Refer to "Derating Curve") | ||||||
WORklNG HUMlDlTY | 20 ~ 90% RH non-condensing | |||||||
STORAGE TEMP., HUMlDlTY | -40 ~ +85ºC, 10 ~ 95% RH non-condensing | |||||||
TEMP. COEFFlClENT | ±0.03%/ºC(0 ~ 50ºC)RH non-condensing | |||||||
VlBRATlON | 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along x,Y, Z axes; Mounting: Compliance to lEC60068-2-6 | |||||||
OPERATlNG ALTlTUDE | 2000 meters | |||||||
OVER VOLTAGE CATEGORY | ; According to EN61558, EN50178,EN60664-1, EN62477-1; altitude up to 2000 meters | |||||||
SAFETY | WlTHSTAND VOLTAGE | l/P-O/P:4kVAC | ||||||
lSOLATlON RESlSTANCE | l/P-O/P:100M Ohms / 500VDC / 25ºC/ 70% RH | |||||||
OTHERS | MTBF | 3724.3k hrs min. Telcordia SR-332(Bellcore); 1166.1k hrs min. MlL-HDBk-217F(25ºC) | ||||||
DlMENSlON | 17.5*90*54.5mm(W*H*D) | |||||||
PACklNG | 74g;160pcs/12.9kg/1.09CUFT | |||||||
NOTE | 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25ºC of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1μf & 47μf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The ambient temperature derating of 3.5ºC/1000m with fanless models and of 5ºC/1000m with fan models for operating altitude higher than 2000m(6500ft). |
60W Ultra Slim Step Shape DlN Rail HDR-60 series |
|||||||||
SPEClFlCATlON | |||||||||
MODEL | HDR-60-5 | HDR-60-12 | HDR-60-15 | HDR-60-24 | HDR-60-48 | ||||
OUTPUT | DC VOLTAGE | 5V | 12V | 15V | 24V | 48V | |||
RATED CURRENT | 6.5A | 4.5A | 4A | 2.5A | 1.25A | ||||
CURRENT RANGE | 0 ~ 6.5A | 0 ~ 4.5A | 0 ~ 4A | 0 ~ 2.5A | 0 ~ 1.25A | ||||
RATED POWER | 32.5W | 54W | 60W | 60W | 60W | ||||
RlPPLE & NOlSE(max.) Note.2 | 80mVp-p | 120mVp-p | 120mVp-p | 150mVp-p | 240mVp-p | ||||
VOLTAGE ADJ. RANGE | 5.0 ~ 5.5V | 10.8 ~ 13.8V | 13.5 ~ 18V | 21.6 ~ 29V | 43.2 ~ 55.2V | ||||
VOLTAGE TOLERANCE Note.3 | ±2.0% | ±1.0% | ±1.0% | ±1.0% | ±1.0% | ||||
LlNE REGULATlON | ±1.0% | ±1.0% | ±1.0% | ±1.0% | ±1.0% | ||||
LOAD REGULATlON | ±1.0% | ±1.0% | ±1.0% | ±1.0% | ±1.0% | ||||
SETUP, RlSETlME | 500ms, 50ms/230VAC 500ms, 50ms/115VAC at full load | ||||||||
HOLD UP TlME(TYP.) | 30ms/230VAC 12ms/115VAC at full load | ||||||||
lNPUT | VOLTAGE RANGE | 85 ~ 264VAC(277VAC operational ) 120 ~ 370VDC(390VDC operational ) | |||||||
FREQUENCY RANGE | 47 ~ 63Hz | ||||||||
EFFlClENCY(TYP.) | 85% | 88% | 89% | 90% | 91% | ||||
AC CURRENT(TYP.) | 1.2A/115VAC 0.8A/230VAC | ||||||||
lNRUSH CURRENT(TYP.) | COLD START 30A/115VAC 60A/230VAC | ||||||||
PROTECTlON | OVERLOAD | 105 ~ 160% rated output power | |||||||
Hiccup mode when output voltage <50%, recovers automatically after fault condition is removed Constant current limiting within 50% ~100% rated output voltage, recovers automatically after fault condition is removed |
|||||||||
OVER VOLTAGE | 5.75 ~ 6.75V | 14.2 ~ 16.2V | 18.8 ~ 22.5V | 30 ~ 36V | 56.5 ~ 64.8V | ||||
Protection type : Shutdown o/p voltage, re-power on to recover | |||||||||
ENVlRONMENT | WORklNG TEMP. | -30 ~ +70ºC (Refer to "Derating Curve") | |||||||
WORklNG HUMlDlTY | 20 ~ 90% RH non-condensing | ||||||||
STORAGE TEMP., HUMlDlTY | -40 ~ +85ºC , 10 ~ 95% RH non-condensing | ||||||||
TEMP. COEFFlClENT | ±0.03%/ºC (0 ~ 50ºC )RH non-condensing | ||||||||
VlBRATlON | 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along x,Y, Z axes; Mounting: Compliance to lEC60068-2-6 | ||||||||
OPERATlNG ALTlTUDE | 2000 meters | ||||||||
OVER VOLTAGE CATEGORY | ; According to EN61558, EN50178,EN60664-1, EN62477-1; altitude up to 2000 meters | ||||||||
SAFETY | WlTHSTAND VOLTAGE | l/P-O/P:4kVAC | |||||||
lSOLATlON RESlSTANCE | l/P-O/P:100M Ohms / 500VDC / 25ºC / 70% RH | ||||||||
OTHERS | MTBF | 3524.8k hrs min. Telcordia SR-332(Bellcore); 927.6k hrs min. MlL-HDBk-217F(25ºC ) | |||||||
DlMENSlON | 52.5*90*54.5mm(W*H*D) | ||||||||
PACklNG | 190g;60pcs/13kg/0.91CUFT | ||||||||
NOTE | 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25ºC of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1μf & 47μf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The ambient temperature derating of 3.5ºC/1000m with fanless models and of 5ºC/1000m with fan models for operating altitude higher than 2000m(6500ft). |
85 ~ 100W Ultra Slim Step Shape DlN Rail HDR - 100 series |
||||||||
SPEClFlCATlON | ||||||||
MODEL | HDR-100-12 | HDR-100-15 | HDR-100-24 | HDR-100-48 | ||||
OUTPUT | DC VOLTAGE | 12V | 15V | 24V | 48V | |||
RATED CURRENT | 7.1A | 6.13A | 3.83A | 1.92A | ||||
CURRENT RANGE | 0 ~ 7.1A | 0 ~ 6.13A | 0 ~ 3.83A | 0 ~1.92A | ||||
RATED POWER | 85.2W | 92W | 92W | 92.2W | ||||
RlPPLE & NOlSE(max.) Note.2 | 120mVp-p | 120mVp-p | 150mVp-p | 240mVp-p | ||||
VOLTAGE ADJ.RANGE | 12 ~ 13V | 15 ~ 17V | 24 ~ 25.5V | 48 ~ 48.7V | ||||
VOLTAGE TOLERANCE Note.3 | ±2.0% | ±1.0% | ±1.0% | ±1.0% | ||||
LlNE REGULATlON | ±1.0% | ±1.0% | ±1.0% | ±1.0% | ||||
LOAD REGULATlON | ±1.0% | ±1.0% | ±1.0% | ±1.0% | ||||
SETUP,RlSETlME | 500ms, 60ms/230VAC 500ms, 60ms/115VAC at full load | |||||||
HOLD UP TlME(TYP.) | 30ms/230VAC 12ms/115VAC at full load | |||||||
lNPUT | VOLTAGE RANGE | 85 ~ 264VAC(277VAC operational ) 120 ~ 370VDC(390VDC operational ) | ||||||
FREQUENCY RANGE | 47 ~ 63Hz | |||||||
EFFlClENCY(TYP.) | 88% | 89% | 90% | 90% | ||||
AC CURRENT(TYP.) | 3A/115VAC 1.6A/230VAC | |||||||
lNRUSH CURRENT(TYP.) | COLD START 35A/115VAC 70A/230VAC | |||||||
PROTECTlON | OVERLOAD | HDR-100 : 102 ~ 110% rated output power ; HDR-100-XXN : 105 ~ 150% rated output power | ||||||
Hiccup mode when output voltage <50%, recovers automatically after fault condition is removed Constant current limiting within 50% ~100% rated output voltage, recovers automatically after fault condition is removed |
||||||||
OVER VOLTAGE | 14.2 ~ 16.2V | 18.8 ~ 22.5V | 30 ~ 36V | 56.5 ~ 64.8V | ||||
Protection type : Shutdown o/p voltage, re-power on to recover | ||||||||
ENVlRONMENT | WORklNG TEMP. | -30 ~ +70ºC(Refer to "Derating Curve") | ||||||
WORklNG HUMlDlTY | 20 ~ 90% RH non-condensing | |||||||
STORAGE TEMP.,HUMlDlTY | -40 ~ +85ºC, 10 ~ 95% RH non-condensing | |||||||
TEMP. COEFFlClENT | ±0.03%/ºC(0 ~ 50ºC)RH non-condensing | |||||||
VlBRATlON | 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along x,Y, Z aXes; Mounting: Compliance to lEC60068-2-6 | |||||||
OPERATlNG ALTlTUDE | 2000 meters | |||||||
OVER VOLTAGE CATEGORY | ; According to EN61558, EN50178,EN60664-1, EN62477-1; altitude up to 2000 meters | |||||||
SAFETY | WlTHSTAND VOLTAGE | l/P-O/P:4kVAC | ||||||
lSOLATlON RESlSTANCE | l/P-O/P:100M Ohms / 500VDC / 25ºC/ 70% RH | |||||||
OTHERS | MTBF | 3271.9k hrs min. Telcordia SR-332(Bellcore); 856.5k hrs min. MlL-HDBk-217F(25ºC) | ||||||
DlMENSlON | 70*90*54.5mm(W*H*D) | |||||||
PACklNG | 0.27kg; 48pcs/13.74kg/0.96CUFT | |||||||
NOTE | 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25ºC of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1μf & 47μf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. Harmonic current test at 90% load for HDR-100-XXN. 5. The ambient temperature derating of 3.5ºC/1000m with fanless models and of 5ºC/1000m with fan models for operating altitude higher than 2000m(6500ft). |
150W Ultra Slim Step Shape DIN Rail HDR - 1 5 0 series |
||||||||||
SPECIFICATION | ||||||||||
MODEL | HDR-150-12 | HDR-150-15 | HDR-150-24 | HDR-150-48 | ||||||
INPUT | DC VOLTAGE | 12V | 15V | 24V | 48V | |||||
RATED CURRENT | 115VAC | 10.2A | 8.55A | 5.31A | 2.72A | |||||
230VAC | 11.3A | 9.5A | 6.25A | 3.2A | ||||||
RATED POWER | 115VAC | 122.4W | 128.3W | 127.4W | 130.6W | |||||
230VAC | 135.6W | 142.5W | 150W | 153.6W | ||||||
RIPPLE & NOISE (max.) Note.2 | 100mVp-p | 120mVp-p | 150mVp-p | 200mVp-p | ||||||
OUTPUT | VOLTAGE ADJ. RANGE | 10.8~ 13.8V | 13.5 ~ 18V | 21.6 ~ 29V | 43.2 ~ 55.2V | |||||
VOLTAGE TOLERANCE Note.3 | ±2.0% | ±1.0% | ±1.0% | ±1.0% | ||||||
LINE REGULATION | ±1.0% | ±1.0% | ±1.0% | ±1.0% | ||||||
LOAD REGULATION | ±1.0% | ±1.0% | ±1.0% | ±1.0% | ||||||
SETUP, RISE TIME | 500ms, 60ms/230VAC 500ms, 60ms/115VAC at full load | |||||||||
HOLD UP TIME (Typ.) | 30ms/230VAC 12ms/115VAC at full load | |||||||||
INPUT | VOLTAGE RANGE | 85 ~ 264VAC (277VAC operational ) 120 ~ 370VDC (390VDC operational ) | ||||||||
FREQUENCY RANGE | 47 ~ 63Hz | |||||||||
EFFICIENCY (Typ.) | 89% | 89.5% | 90.5% | 90.5% | ||||||
AC CURRENT (Typ.) | 3A/115VAC 1.6A/230VAC | |||||||||
INRUSH CURRENT (Typ.) | COLD START 35A/115VAC 70A/230VAC | |||||||||
PROTECTION | OVERLOAD | 105 ~ 135% rated output power | ||||||||
Hiccup mode when output voltage <50%, recovers automatically after fault condition is removed Constant current limiting within 50% ~100% rated output voltage, recovers automatically after fault condition is removed |
||||||||||
OVER VOLTAGE | 14.2 ~ 16.2V | 18.8 ~ 22.5V | 30 ~ 36V | 56.5 ~ 64.8V | ||||||
Protection type : Shutdown o/p voltage, re-power on to recover | ||||||||||
ENVIRONMENT | WORKING TEMP. | -30 ~ +70ºC (Refer to "Derating Curve") | ||||||||
WORKING HUMIDITY | 20 ~ 90% RH non-condensing | |||||||||
STORAGE TEMP., HUMIDITY | -40 ~ +85ºC, 10 ~ 95% RH non-condensing | |||||||||
TEMP. COEFFICIENT | ±0.03%/ºC (0 ~ 45ºC) RH non-condensing | |||||||||
VIBRATION | 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X,Y, Z axes; Mounting: Compliance to IEC60068-2-6 | |||||||||
OPERATING ALTITUDE | 2000 meters (Note 4 ) | |||||||||
OVER VOLTAGE CATEGORY | ;According to EN62368 ,EN61558 , EN50178 ,EN60664- 1 , EN62477- 1;altitude up to 2000 meters | |||||||||
SAFETY STANDARDS | IEC62368-1, UL62368-1, UL61010, TUV BS EN/EN61558-2-16, BS EN/EN61558-1, EACTPTC 004 approved; Design refer to BS EN/EN50178, TUV BS EN/EN62368-1 |
|||||||||
SAFETY | WITHSTAND VOLTAGE | I/P-O/P:4KVAC | ||||||||
ISOLATION RESISTANCE | I/P-O/P:100M Ohms / 500VDC / 25ºC/ 70% RH | |||||||||
OTHERS | MTBF | 3046.3K hrs min. Telcordia SR-332 (Bellcore) ; 535.9K hrs min. MIL-HDBK-217F (25ºC) | ||||||||
DIMENSION | 105*90*54.5mm (W*H*D) | |||||||||
PACKING | 0.31Kg; 32pcs/11Kg/1.0CUFT | |||||||||
NOTE | 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25ºC of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1μf & 47μf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The ambient temperature derating of 3.5ºC/1000m with fanless models and of 5ºC/1000m with fan models for operating altitude higher than 2000 (6500ft). 5. when the input voltage is 230VAC,delivers EMl Class B for radiated emission for the power supply; when the input voltage is 110VAC, delivers EMl Class A for radiated emission for the power supply. 6. Harmonic current test at 70% load . |